Testing, mix design, and durability
This chapter covers the following:
- Concrete strength testing requirements and sampling criteria
- Definition and evaluation of compressive strength tests
- Acceptable strength criteria and structural adequacy requirements
- Field-cured cylinders and core testing standards
- Concrete mix design parameters, including yield and absolute volume
- Water-cement ratio and cementitious material components
- Aggregate moisture conditions and calculations
- Aggregate properties, including density, absorption, and specific gravity
- Concrete maturity and time-temperature relationships
- Concrete exposure categories and classification systems
Concrete strength testing requirements
Sampling frequency
- Samples for strength tests of each class of concrete placed each day shall be taken not less than:
- Once per day, and
- Once for each of concrete, or
- Once for each of slab or wall surface area (whichever governs).
Small quantities
- When total quantity of a given class of concrete is less than 50 yd³:
- Strength tests are not required if evidence of satisfactory strength is submitted and approved by the building official.
Strength test definition
- A strength test is the average compressive strength of:
- At least two 6 in. × 12 in. cylinders, or
- At least three 4 in. × 8 in. cylinders
- Cylinders are made from the same sample and tested at 28 days, or at the designated test age.
Specified strength notation
- Let:
Acceptable strength criteria
The strength level of an individual concrete class is satisfactory if:
- Three-test average requirement:
-
No single test underperformance:
- If:
- If:
Field-cured cylinders
-
If field-cured cylinder strength at test age is less than 85% of that of companion lab-cured cylinders, the procedures for protecting and curing the in-place concrete must be improved.
-
Exception: This 85% limit does not apply if field-cured strength exceeds:
Core tests for existing structures
- Concrete cores from structures must be tested no earlier than 48 hours nor later than 7 days after coring, and at least 5 days after last being wetted (unless otherwise approved by the building official), per ACI 318 / ASTM C42.
Structural adequacy criteria
Let the average of 3 core strengths be denoted as .
Concrete is structurally adequate if:
- Average strength:
- Minimum single core strength:
Concrete mix design parameters
Yield
Yield is the volume of fresh concrete produced from a batch:
Absolute volume
The absolute volume of a concrete ingredient is calculated as:
Example: Absolute volume and yield
A batch contains 500 lb of cement (), 235 lb of water (), 1200 lb of SSD fine aggregate (), and 1800 lb of SSD coarse aggregate (). Using , find the yield.
- Cement:
- Water:
- Fine aggregate:
- Coarse aggregate:
Answer: yield (about )
Aggregate moisture conditions
Relative densities of aggregates are taken under saturated surface-dry (SSD) conditions.
- Total moisture (%)
- Absorbed moisture (%) (also called the aggregate’s absorption)
- Free moisture (%)
Example: Aggregate moisture content
A fine aggregate sample has a wet mass of 1050 g, an oven-dry mass of 1000 g, and an SSD mass of 1020 g. Find the total, absorbed, and free moisture.
- Total moisture:
- Absorbed moisture:
- Free moisture:
Answer: the aggregate carries more water than SSD requires, so that amount must be subtracted from the batch water.
Water-cement ratio
The water-cementitious material ratio (w/c) is defined as:
Cementitious materials may include:
- Portland cement
- Blended cement
- Fly ash
- Slag cement
- Silica fume
- Natural pozzolans
Example: Water-cementitious materials ratio
A mix uses 235 lb of water and 517 lb of total cementitious material per cubic yard. Find .
Answer:
Aggregate properties in concrete mix design
Mix designs use the SSD condition as the reference point, since that’s what separates water absorbed inside the aggregate (which doesn’t change the amount of mixing water needed) from water sitting on its surface (which does). The properties below build on that same reference condition, and on the total, absorbed, and free moisture percentages defined above.
SSD (saturated-surface-dry)
- The condition in which the permeable pores of aggregate particles are filled with water as if submerged, but without any free water on the surface of the particles.
Density and specific gravity
The density measures below differ in two ways: which mass they use (oven-dry or SSD) and which volume they use. None of them include the voids between particles. The key distinction to keep straight is which pores count as part of the particle’s volume: oven-dry and SSD density count all pores, permeable and impermeable, while apparent density counts only the impermeable ones.
The following table compares three density measures by the mass and volume each one uses.
| Term | Mass used | Volume used |
|---|---|---|
| Density (oven-dry) | Oven-dry mass, | Particle volume, including permeable and impermeable pores |
| Density (SSD) | SSD mass, (oven-dry mass plus absorbed water) | Particle volume, including permeable and impermeable pores |
| Apparent density | Oven-dry mass, | Particle volume, including impermeable pores only |
Bulk specific gravity
Both bulk specific gravity bases below use the same denominator: the mass of water equal to , the aggregate particle volume including all permeable and impermeable pores. The two bases differ only in which mass goes in the numerator.
Oven-dry basis:
SSD basis:
- Typical range for normal-weight aggregates:
Concrete maturity
Concrete maturity can be estimated using the Time-Temperature Factor method:
where
- = maturity index (-hours)
- = average concrete temperature () during time interval
- = datum temperature (), usually unless otherwise specified
- = elapsed time ()
- = time intervals ()
Example: Maturity index
Concrete cures at for 6 hours, then for 4 hours. Using a datum temperature of , find the maturity index.
Answer:
Concrete exposure categories and classes
Freezing and thawing (F)
| Class | Condition |
|---|---|
| F0 | Concrete not exposed to freezing-and-thawing cycles |
| F1 | Concrete exposed to freezing-and-thawing cycles with limited exposure to water |
| F2 | Concrete exposed to freezing-and-thawing cycles with frequent exposure to water |
| F3 | Concrete exposed to freezing-and-thawing cycles with frequent exposure to water and exposure to deicing chemicals |
Other exposure categories
ACI 318 defines three more exposure categories using the same tiered structure as the F-classes above:
- Sulfate (S0-S3): based on water-soluble sulfate in soil or dissolved sulfate in water, ranging from negligible exposure (S0) to severe exposure (S3, above 2.00% in soil or 10,000 ppm in water).
- In contact with water (W0-W2): from concrete kept dry in service (W0), to concrete in contact with water where low permeability isn’t required (W1), to concrete in contact with water where low permeability is required (W2).
- Corrosion protection of reinforcement (C0-C2): from concrete dry or protected from moisture (C0), to concrete exposed to moisture without an external chloride source (C1), to concrete exposed to moisture and an external chloride source such as deicing chemicals or seawater (C2).
For example, a bridge pier exposed to seawater spray falls under C2 (moisture plus an external chloride source), while an interior column protected from moisture falls under C0.
The FE exam more often tests recognizing which category and class a scenario falls into than exact threshold values, so focus on the F-class table above as the model for how each category’s classes are structured.